Smarter Power Distribution. Zero Disruption. Total Visibility. Sm@rtGear IE is an intelligent power distribution solution designed for the demands of industrial environments with real-time monitoring, predictive diagnostics, and remote-control capabilities.
ATO Points
This Data Point subtopic represents the ATO data provided by the Sm@rtgear IE DPU (or other polling applications) that are being sent over the databus. In order to subscribe to these data points, the subscription will need the ATO data category subtopic at the beginning of the topic string, "31".
31/Data Point/Device Type/Device Name/Device Source
flowchart LR
A[Category: 31] --> B[Data Point - Numeric]
B --> C[Device Type - Numeric]
C --> D[Device Name - String]
D --> E[Device Source - String]
Point Family
Each datapoint is grouped into a broader "family" of other points that measure different aspects of the same thing. This categorization helps in terms of data measurement and understanding the different measurements being taken. Below are all the data point families for the ATO Data subtopic.
flowchart LR
A[Breaker Statuses<br>1-7]
A ~~~ B[Breaker Failure Statuses<br>8-15]
B ~~~ C[Source<br>16-17]
C ~~~ D[System<br>18-23]
Breaker Statuses
Point Name (Unit) | Number | Data Type | Overall Topic | App Source(s) | Ingested Source(s) |
---|
isOpen | 1 | Boolean | 31/1/{DEVICE TYPE}/{DEVICE NAME}/{DEVICE SOURCE} | SmartDPU | |
isClosed | 2 | Boolean | 31/2/{DEVICE TYPE}/{DEVICE NAME}/{DEVICE SOURCE} | SmartDPU | |
isRTC | 3 | Boolean | 31/3/{DEVICE TYPE}/{DEVICE NAME}/{DEVICE SOURCE} | SmartDPU | |
isConnected | 4 | Boolean | 31/4/{DEVICE TYPE}/{DEVICE NAME}/{DEVICE SOURCE} | SmartDPU | |
isBellAlarm | 5 | Boolean | 31/5/{DEVICE TYPE}/{DEVICE NAME}/{DEVICE SOURCE} | SmartDPU | |
isSync | 6 | Boolean | 31/6/{DEVICE TYPE}/{DEVICE NAME}/{DEVICE SOURCE} | SmartDPU | |
isSourceAvailable | 7 | Boolean | 31/7/{DEVICE TYPE}/{DEVICE NAME}/{DEVICE SOURCE} | SmartDPU | |
Breaker Failure Statuses
Point Name (Unit) | Number | Data Type | Overall Topic | App Source(s) | Ingested Source(s) |
---|
isVoltageFailure | 8 | Boolean | 31/8/{DEVICE TYPE}/{DEVICE NAME}/{DEVICE SOURCE} | SmartDPU | |
isFailToClose | 9 | Boolean | 31/9/{DEVICE TYPE}/{DEVICE NAME}/{DEVICE SOURCE} | SmartDPU | |
isFailToOpen | 10 | Boolean | 31/10/{DEVICE TYPE}/{DEVICE NAME}/{DEVICE SOURCE} | SmartDPU | |
isFailtoSync | 11 | Boolean | 31/11/{DEVICE TYPE}/{DEVICE NAME}/{DEVICE SOURCE} | SmartDPU | |
isExternalTrip | 12 | Boolean | 31/12/{DEVICE TYPE}/{DEVICE NAME}/{DEVICE SOURCE} | SmartDPU | |
isNotConnect | 13 | Boolean | 31/13/{DEVICE TYPE}/{DEVICE NAME}/{DEVICE SOURCE} | SmartDPU | |
isNotRTC | 14 | Boolean | 31/14/{DEVICE TYPE}/{DEVICE NAME}/{DEVICE SOURCE} | SmartDPU | |
isbellAlarm | 15 | Boolean | 31/15/{DEVICE TYPE}/{DEVICE NAME}/{DEVICE SOURCE} | SmartDPU | |
Source
Point Name (Unit) | Number | Data Type | Overall Topic | App Source(s) | Ingested Source(s) |
---|
sourceFailure | 16 | Boolean | 31/16/{DEVICE TYPE}/{DEVICE NAME}/{DEVICE SOURCE} | SmartDPU | |
sourceAvailable | 17 | Boolean | 31/17/{DEVICE TYPE}/{DEVICE NAME}/{DEVICE SOURCE} | SmartDPU | |
System
Point Name (Unit) | Number | Data Type | Overall Topic | App Source(s) | Ingested Source(s) |
---|
sourceFailure | 16 | Boolean | 31/16/{DEVICE TYPE}/{DEVICE NAME}/{DEVICE SOURCE} | SmartDPU | |
sourceAvailable | 17 | Boolean | 31/17/{DEVICE TYPE}/{DEVICE NAME}/{DEVICE SOURCE} | SmartDPU | |
isSystemModeAuto | 18 | Boolean | 31/18/{DEVICE TYPE}/{DEVICE NAME}/{DEVICE SOURCE} | SmartDPU | |
isRetransferAuto | 19 | Boolean | 31/19/{DEVICE TYPE}/{DEVICE NAME}/{DEVICE SOURCE} | SmartDPU | |
isRetransferBypass | 20 | Boolean | 31/20/{DEVICE TYPE}/{DEVICE NAME}/{DEVICE SOURCE} | SmartDPU | |
isClosedTransition | 21 | Boolean | 31/21/{DEVICE TYPE}/{DEVICE NAME}/{DEVICE SOURCE} | SmartDPU | |
isAlarmReset | 22 | Boolean | 31/22/{DEVICE TYPE}/{DEVICE NAME}/{DEVICE SOURCE} | SmartDPU | |
isUpsAlarm | 23 | Boolean | 31/23/{DEVICE TYPE}/{DEVICE NAME}/{DEVICE SOURCE} | SmartDPU | |